Figure 7-3: Custom alarm level
A. Low saturation
B. Normal operation
C. High saturation
1. Transmitter failure, hardware, or software alarm in LO position.
2. Transmitter failure, hardware, or software alarm in HI position.
7.4 
Safety Instrumented Systems (SIS) operation
and maintenance
7.4.1 
Proof-tests
Emerson recommends the following proof-tests.
If you find an error in safety or functionality, you can document proof-test results and
corrective actions taken at Emerson.com/ReportFailure.
 WARNING
Only allow qualified personnel to perform proof-tests.
Verify the Security switch is in the Unlock position during the proof-test and reposition it in
the Lock position after the proof-test.
7.4.2 
Perform a guided proof-test
If you select the guided proof-test option, the Rosemount 3051 will support a feature that
can perform a guided partial or comprehensive proof-test.
This feature walks you through the necessary steps to perform a proof-test. The alarm
levels and required steps will be provided without the need to look them up.
To access the guided proof-test option:
Procedure
Go to Device Settings → Calibration → Proof Test → Perform Proof Tests.
The guided proof-test option comes with a proof-test log. This log stores the ten most
recent proof-tests directly in the transmitter. The log includes time stamp, communication
source, Pass/Fail result, and any user-defined notes.