Emerson Rosemount 3051 Manual page 22

Pressure transmitter with 4-20 ma hart protocol
Hide thumbs Also See for Rosemount 3051:
Table of Contents

Advertisement

Configuration
March 2023
Table 2-5: Entered values for flow rate configuration example
Parameter
Flow rate units
Entered flow rate
Pressure at flow rate
Low flow cut-off
Pressure cut-off value
Pressure cut-in value
Figure 2-5: Asset Management Solutions (AMS) Configuration screen for flow rate
example
2.6.2 
Configuring for totalized flow
The flow totalizer will track the amount of flow that has passed your measurement point
over time. The totalized flow output tracks the configured flow rate and will require the
following inputs:
Totalizer units
Flow unit of time
Example
For a flow rate of USGPH, the totalizer unit would be USGAL, and the flow unit of time
would be hours.
The flow unit is displayed on the communication device for convenience when you
configure totalized flow on a communication device.
22
Unit of measure associated with the mass or volume component of the
flow rate. Six characters maximum.
Unit of measure associated with the time component of the flow rate.
Manual
00809-0100-4007
Value
USGPH
20,000 USGPH
100 inH
O at 68 °F
2
Cut-off mode:
On
0.5 inH
O at 68 °F
2
0.5 inH
O at 68 °F
2
Rosemount 3051