Hardware installation
March 2023
3.4.2 
Impulse piping
Mounting requirements
Impulse piping configurations depend on specific measurement conditions. Refer to
3-9
for examples of the following mounting configurations:
Liquid measurement
Place taps to the side of the line to prevent sediment deposits on the transmitter's
process isolators.
Mount the transmitter beside or below the taps so gases can vent into the process line.
Mount drain/vent valve upward to allow gases to vent.
Gas measurement
Place taps in the top or side of the line.
Mount the transmitter beside or above the taps so liquid will drain into the process line.
Steam measurement
Place taps to the side of the line.
Mount the transmitter below the taps to ensure that the impulse piping will stay filled
with condensate.
In steam service above 250 °F (121 °C), fill impulse lines with water to prevent steam
from contacting the transmitter directly and to ensure accurate measurement start-up.
NOTICE
For steam or other elevated temperature services, it is important that temperatures at the
process connection do not exceed the transmitter's process temperature limits.