5.3.8.1
Activating and configuring the block inputs
Fig. 20: Function block input settings
The following parameters can be set:
• Deactivated: The input is not used
• Single-channel: The inputs are linked independent of each other
• Two-channel: The inputs are monitored for equality or inequality, depending on the contact type
setting. A Discrepancy Time can be set for monitoring the two inputs for simultaneous switching.
• Make Contact: Contact type setting
• Break Contact: Contact type setting
The inputs are now activated.
Fig. 21: Activated inputs
The inputs can now be linked.
KL6904
Version: 3.0.0
Operation
39