2: Point Programming For The Internal Or External Power Module - Honeywell IFP-75 Installation & Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Programming
Type
Function
Selection
RELAY
OUTPUT PT
AUX RESET
AUX DOOR
9.5.2 Point Programming for the Internal or External Power Module
To program for an internal or external power module points, follow these steps:
1.
Enter the Installer Code.
2.
Select 7 to access the Program Menu.
3.
Press 4 to enter the Point Menu.
4.
Press the up or down arrows to select the desired module. Press ENTER.
Refer to Section 8.5 for the available choices.
5.
Enter the number of the circuit or point you want to edit. Refer to Table 9.5 for available selections.
6.
Press ENTER.
7.
To select the Type, press the up or down arrows, then, press ENTER.
8.
To select the Function, press the up or down arrows, then, press ENTER.
9.
To select the Group, press the up or down arrows, then, press ENTER.
10. To edit the Point Name, press the right arrow to skip the Point Name Edit. See Section 9.5.
11. Repeat Steps 1 through 10 for all circuits.
96
Latching Option
Select Group
Output Point, a general use relay type. Use for applications requiring a relay, such as
elevator recall.
Use for auxiliary power, resettable applications. See Section 4.13.2 (subsection,
Resettable Power) to learn how this option operates.
Use for auxiliary power, door holder applications. For example, if you were using an
auxiliary power supply for door holders, you would use this option. See Section 4.13.2
(subsection, Door Holder Power) for a description of how this option operates.
Table 9.4 Point Programming for Internal SLC Module (Continued)
IFP-75/IFP-75HV Installation/Operation Manual — P/N LS10147-001SK-E:D 06/25/2021