Honeywell 6820 Manual page 98

Addressable fire alarm conrol panel
Table of Contents

Advertisement

Programming
Type Selection
UNUSED
DETECTOR
SUP DET
CO SMOKE DETECTOR
W-DETECTOR
W-SUP DET SWITCH
SWITCH
98
Function
Latching Option
PHOTO
ION
HEAT
PHOTO DUCT
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
PHOTO
Latching
Non Latching
ION
HEAT
PHOTO DUCT
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
CO ALRM /
FIRE ALRM
CO ALRM /
FIRE SUPR
CO SUPR /
FIRE ALRM
CO SUPR /
Latching
FIRE SUPR
Non Latching
PHOTO
PHOTO-HEAT
HEAT
Same as W-Detector
Latching
Non Latching
MANUAL PULL
WATERFLOW
Latching
Non Latching
FIRE SUPERVISORY Latching
Non Latching
FIRE DRILL
Table 8.5 Programming Options for 6815 Modules
Select for SLC points that are unused.
Spot photoelectric detectors.
Spot ION detectors
Spot heat detector.
Duct photoelectric detector.
Acclimate photoelectric detector.
High temperature heat detector.
Photoelectric detector with heat sensor.
Beam smoke detector.
Use this option when you want a detector to indicate a supervisory alarm.
No Accessory Base, Sounder base, Relay Base, or Intelligent Sounder base.
Bases can be set for Single station or Multi station, Silence or Non-Silence,
Latching or non-latching. Intelligent sounder bases can have volume set for
high or low.
Supervisory switches can be latching or non-latching.
Wireless photoelectric detectors
Wireless heat detector
Wireless heat detector
Wireless photoelectric detectors
Use this switch type for manual pull stations. This input is always latched. The
switch can clear only when an alarm is reset. This switch type has the highest
fire priority; it overrides any other type of fire alarm.
Use this switch type for monitoring water flow in a sprinkler system. Switch
closure will cause a sprinkler alarm. Water flow switches can be programmed
as latching or non-latching.
You can program a delay of up to 90 seconds to be used with a water flow
switch. The delay allows for normal, brief changes in sprinkler system water
pressure. The water flow alarm will not activate unless the switch is active for
the programmed delay time.
If a delay is used, the system begins counting down when the switch closes. If
the switch opens (restores) before the timer expires, a water flow alarm is not
generated. If the water flow switch remains closed after the timer expires, a
water flow alarm will be generated.
Use this switch type for tamper monitoring of sprinklers and other fire
protection devices. If a contact closes, a sprinkler supervisory event will be
generated. Supervisory switches can be latching or non-latching.
System-level, non latching switch. This switch is an alternative way of causing
a fire drill. It has the same operation as the fire drill option available from the
annunciator. When the switch is activated, a fire drill begins; when the switch
is de-activated, the fire drill ends.
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022