System Operation
Operating
Occurs When
Mode
Supervisory
The system detects a
supervisory condition.
A Supervisory with a
CO detector.
Trouble
A system trouble
condition occurs.
A trouble condition
with a CO detector
Pre-alarm
A single detector trips
in a 2-Count zone.
(2-Count means two
detectors must trip
before an alarm is
reported.)
122
System Behavior
The system will report events to the central station.
The onboard annunciator sounds a loud, pulsing beep
to distinguish supervisory signals. For fire supervisory
signals, the sequence is one second on, one second
off. For EVS supervisory signals, the sequence is two
seconds on, three seconds off.
The SUPERVISORY LED flashes.
The LCD displays a screen similar to this one.
FIRE: SUPERVISORY
Supervisory Sw
SBUS_97 MODULE_2
1 of 1
Pressing the right arrow key or Info to display the
location macro, date/time stamp, and site/panel, if
applicable.
Site 1
CO: SUPR
[Press for status]
Press the right arrow key or Info to view the type and
location of the Supervisory event. The message will
alternate with the time/date display.
The system will report events to the central station.
The onboard annunciator sounds a loud, pulsing beep
in the sequence one second on, nine seconds off.
The SYSTEM TROUBLE LED flashes.
The LCD displays a screen similar to this one.
FIRE: TROUBLE
1 of 1
Press the right arrow key or Info to display the location
macro, date/time stamp, and site/panel, if applicable.
Site 1
CO: TROUBLE
[Press for status]
Press the right arrow key or Info to view the type and
location of the Trouble event. The message will
alternate with the time/date display.
The touchpad piezo beeps.
The LCD displays a screen similar to this one.
FIRE: PREALARM
Det-Photo
SBUS_97 SENSOR_33
1 of 1
Press the right arrow key or Info to display the location
macro, date/time stamp, and site/panel, if applicable.
Table 9.4 Panel Operating Modes (Continued)
Press the down arrow to view the fire supervisory
condition. A screen similar to this one displays.
SUPERVSY: MAN_PULL
MODULE_33 POINT_2
[Z002] [M33]
Press SILENCE and enter an Access Code (or activate
the key) to silence the annunciator.
Once the supervisory condition has been corrected, the
Info>
system will restore automatically.
Press down arrow to view the fire trouble. A screen
similar to this one displays.
zone #
trouble
type
In this case, the panel does not see a
detector that should be on the loop.
Info>
Press SILENCE to silence the annunciator.
Once the trouble condition has been fixed, the system
will restore itself automatically.
Press down arrow to view the Prealarm. A screen similar
to this one displays.
PREALARM:SMOKE-PHOT
MODULE_33 POINT_2
[Z002] [M33]
Info>
All system operations are available in this mode.
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Operation Mode Behavior
In This Mode You Can
1 of 1
showing 1 of 1 event
TROUBLE: CO Smoke
SBUS_33 SENSOR_2
[Z002] [M33:S002]
Missing
5 of 8
showing 5 of 8 events
1 of 1
showing 1 of 1 event
device
type
device
type
module/
point
device
type