STX/SC: PROCEDURE TO CLEAR MAINTENANCE ALARMS
The super charged series machines have an alarm list of maintenance items which will automatically appear after
2000 hrs. of operation. These alarms are not sensing a fault within the system, but rather acting as a reminder to
perform certain maintenance tasks. In some cases the interval at which the alarms are displayed may be sooner than
the item actually requires. When a maintenance item occurs, call Mazak with the current hour reading and confirm
whether or not the alarm merits attention. The procedure below will reset maintenance alarms.
Turn off laser power, high voltage and power at the operating panel.
1>
2>
Turn on the power at the operating panel.
Press any key once, to clear the maintenance alarm.
3>
4>
Press the second blank menu key from the right. ( do not "HOME" or press any other keys).
5>
Press "input"
6>
Press the blue "D" (DISPLAY) key.
7>
Press the "parameter" menu key.
8>
Press the "NC" menu key.
9>
Press the "next page" menu key until parameter no. 5111 is present.
10>
Cursor to parameter 5111
11>
Press the "ADJ" menu key.
12>
Enter the current value for 5111 + 2000
Example:
13>
Press "INPUT"
14>
The alarm will now occur after the next 2000 hours has elapsed.
if 5111 = 2000
then enter 4000