Cable connection

The cable must be secured to a part that does not move relative to the readhead using a
suitable clip within 50 mm of exiting the readhead with a minimum bend radius > 10 mm.
Cable rolling radius must be > 25 mm when the cable is routed through moving
trunking / a cable chain.
NOTE: UHV cables are for static use only.
The cable must be routed to avoid all moving parts of the machinery and the readhead itself.
Route the cable away from operating environments that will exceed the EMC limits defined in
IEC 61800-5-2: Annex E second environment.
Use only Renishaw approved cables between the readhead and the interface.
The customer is responsible for verifying the product function where the cable has been
re-terminated, including the installation of extension cables. This includes EMC performance
of the installed system defined in IEC 61800-5-2: Annex E second environment.
The sine and cosine signals must be connected as described in
page 45.