Fig. 19: Worst case response time
It is assumed that a signal change takes place at the sensor, and that this is passed to the input. A
communication error occurs just at the moment when the signal is to be passed to the communication
interface. This is detected by the logic once the watchdog time of the communication link has elapsed. This
information should then be passed on to the output, resulting in a further communication error. This fault is
detected at the output once the watchdog time has elapsed, resulting in shutdown.
This results in the following formula for the worst-case response time:
ReactionTime
=
WD
+
max
Comm
with
ReactionTime
=
2 *15
ms
+
max
5.2.6

Tested EL1904 devices

The following list contains devices that were tested together with the EL1904 TwinSAFE terminal. The
results only apply for the current device hardware version at the time of testing. The tests were carried out in
a laboratory environment. Modifications of these products cannot be considered here. If you are unsure
please test the hardware together with the TwinSAFE terminal.
Manufacturer
Type
SICK
C4000
SICK
S3000
Wenglor
SG2-14ISO45C1
Leuze
lumiflex ROBUST 42/43/44
Schmersal
BNS250-11ZG
ifm
GM701S
Keyence
SL-V (with PNP cable set)
The tests were carried out as function tests only. The information provided in the respective manufacturer
documentation remains valid.
EL1904
WD
+
RT
Comm
Actuator
20
ms
=
50
ms
Version: 3.0.0
Comment
Safety light curtain
Safety laser scanner
Safety light grids
Safety light barriers
Safety switch
Inductive safety sensor
Safety light curtain
Operation
37