Fig. 18: Worst case response time
It is assumed that a signal change takes place at the sensor, and that this is passed to the input. A
communication error occurs just at the moment when the signal is to be passed to the communication
interface. This is detected by the logic once the watchdog time of the communication link has elapsed. This
information should then be passed on to the output, resulting in a further communication error. This fault is
detected at the output once the watchdog time has elapsed, resulting in shutdown.
This results in the following formula for the worst-case response time:
ReactionTime
=
WD
+
max
Comm
with
ReactionTime
=
2 *15
ms
+
max
4.2.6

Tested EL2904 devices

The following list contains devices that were tested together with the EL2904 TwinSAFE terminal. The
results only apply for the current device hardware version at the time of testing. The tests were carried out in
a laboratory environment. Modifications of these products cannot be considered here. If you are unsure
please test the hardware together with the TwinSAFE terminal.
Manufacturer
Type
Beckhoff
AX5801
Beckhoff
AX2000 AS option
Siemens
SIRIUS series S00
3RT1016-1BB42
Telemecanique
LP1K09
The tests were carried out as function tests only. The information provided in the respective manufacturer
documentation remains valid.
Recommended protective circuits
We recommend R/C or diode-based protective circuits for these devices.
Varistor-based protective circuits should not be used.
EL2904
WD
+
RT
Comm
Actuator
20
ms
=
50
ms
Version: 2.3.0
Comment
TwinSAFE Drive option card: safe restart lock
safe restart lock
Contactor
Contactor
Operation