Technical data
Setting elements The EWG is housed in the actuator switch compartment. The switch compartment

11.3.1 Set measuring range

7)
Power supply possible via: AC, AM actuator controls or external power supply
8)
Depending on temperature range of the actuator: refer to name tag
Table 17: EWG 01.1
Data
Output current I
a
7)
Power supply U
V
Max. current consumption
Max. load R
B
Impact of power supply
Load influence
Temperature impact
8)
Ambient temperature
must be opened to perform any settings. Refer to
All settings are made via the two push buttons [S1] and [S2].
Figure 35: View on control unit when switch compartment is open
[S1]
LED
[1]
[S1]
Push button: Set 0/4 mA
LED
Optical aid for setting
[2]
Measuring point (–) 0/4 – 20 mA
The output current (measuring range 0 – 20 mA) can be checked at measuring points
[1] and [2].
Table 18: Short overview on push button functions
Push but-
Function
tons
[S1] + [S2]
→ press simultaneously for 5 s: Activate setting mode
→ press in setting mode for 3 s: Set 4 mA
→ press in setting mode for 6 s: Set 0 mA (only possible for 3-/4-wire version)
[S1]
→ press in operation for 3 s: Switch on/off LED end position signaling
→ touch in end position: Reduce current value by 0.02 mA
→ press in setting mode for 3 s: Set 20 mA
[S2]
→ press in operation for 3 s: Switch on/off LED end position signaling
→ touch in end position: Increase current value by 0.02 mA
For measuring range setting, voltage must be applied at the position transmitter.
For output current verification, connect a test device for 0 – 20 mA to measurement
points (+/–) (for 2-wire systems, connecting a test device is required).
Commissioning (optional equipment settings)
3-wire and 4-wire systems
0 – 20 mA, 4 – 20 mA
24 V DC (18 – 32 V)
LED off= 26 mA,
LED on = 27 mA
600 Ω
< 0.1 ‰/K
–76 °F to 176 °F [–60 °C to +80 °C]
Open switch compartment
[S2]
Push button: Set 20 mA
[1]
Measuring point (+) 0/4 – 20 mA
2-wire system
4 – 20 mA
24 V DC (18 – 32 V)
20 mA
(U
– 12 V)/20 mA
V
0.1 %
0.1 %
[} 27].
[S2]
[2]
35