Servicing and maintenance
Notes relating to mainte-
nance

13.4 Disposal and recycling

42
Generally after 4 to 6 years for modulating duty.
Generally after 6 to 8 years if operated frequently (open-close duty).
Generally after 10 to 12 years if operated rarely (open-close duty).
We recommend replacing the seals when changing the grease.
Perform visual inspection of actuator and mounted accessories. Ensure that no
outside damage, changes or leakage of grease and oil are visible.
Check actuator for unusual running or grinding noise or vibration which might be
an indication of bearing or gear damage.
The electric connection cables must be without damage and wired correctly.
Thoroughly touch up any possible damage to painting to prevent corrosion. Origi-
nal paint in small quantities can be supplied by AUMA.
Check whether Ex connections are fastened correctly.
Take care of possible discoloration of the terminals and wires. This would indicate
an increased temperature.
For Ex housings, pay special attention to a possible collection of water. This may
originate from "breathing" due to severe temperature variations (e. g. change of
night and day), from damaged seals etc. Remove any water immediately.
The process temperature range must be within the range of the specified ambient
temperature.
Check the flame path gaps of flameproof enclosures for dirt and corrosion.
Since the dimensions of all flameproof joints are strictly defined and inspected, no
mechanical work (such as grinding) shall be performed on them. The flameproof
joints should be cleaned suitably.
Consult manufacturer for indications regarding flameproof joints.
Repair interventions on flameproof joints is not permitted.
Prior to fitting, preserve joint surfaces with an acid-free corrosion protection agent
(e. g. Esso Rust-BAN 397).
Handle all housing covers with care and check seals
All cable and motor protection components have to be checked.
If defects impairing the safety are detected during maintenance, repair measures
have to be initiated without delay.
Any kind of surface coating for the flameproof joints is not permitted.
When exchanging parts, seals etc. only original spare parts shall be used.
Cables and wire entries, blanking plug, cable glands, plugs etc. have to be
checked for correct tightness and sealing. Consider torques according to manufac-
turer's details. If required, re- place the components. Only use components with
appropriate Ex approval.
Our devices have a long service life. However, they have to be replaced at one point
in time. The devices have a modular design and may, therefore, easily be separated
and sorted according to materials used, i.e.:
Electronic scrap
Various metals
Plastic materials
Greases and oils
The following generally applies:
Generally, greases and oils are hazardous to water and must not be released into
the environment.