Vibration Isolation (Accessory)

Figure 13: Ceiling Hung with Rubber Isolators - Unit Sizes
006-050 (Sizes 006-020 shown).
Hanger Rods (by others)
Factory Ordered
Rubber Isolators
Figure 14: Ceiling Hung Spring Isolation - Unit Sizes 030,
040, 050.
Spring Isolators
(by others)
Hanging Rods (by others)
Unit Sizes
030, 040, 050
Double Nut(s)
Note: Spring isolation is recommended on sizes 030, 040 and 050
as these units do not have any internal vibration isolation.

Mounting the Unit on the Floor

Vertical units are all floor-mounted, and horizontal units may be
floor-mounted as well.
www.DaikinApplied.com
Spring Mount—Sizes 030, 040, 050
Factory ordered spring isolators are recommended for
horizontal units, sizes 030, 040 and 050. The isolators should
all be at the same height opening. If adjustments are required,
loosen the 5/16" capscrew on top of the isolator and turn the
adjusting bolt to lower or raise the unit base. Retighten the
capscrew when adjustments are completed. See
Figure 15: Floor Mounted Spring Isolation - Unit Sizes 030,
040, 050.
Double Nut(s)
(by others)
13
Unit Sizes
030, 040, 050
Spring Isolators
IM 1267-7 • PRECISELINE AIR HANDLER
Installation