7. Slide out motor from fan housing.
Vertical Unit Sizes 030 - 050
(Welded Aluminum Airfoil Plenum Fans)
1. Turn the switch disconnect handle to the off position.
NOTE: Dual fan assembly shown.
2. Remove the screws holding the access panel in place.
IM 1267-7 • PRECISELINE AIR HANDLER
3. Detach the low-voltage and power wires from the motor
by releasing the plastic connectors.
NOTE: Remember the motor orientation when installing a
new fan. Matching the motor orientation will ensure
wires can reach the connectors of the new motor.
4. Secure supports to the metal bar frame.
FAN SLED ASSEMBLY IS HEAVY!
Failure to use the proper lifting equipment to support the weight of the sled
assembly can cause property damage, personal injury or death. Supports
should be able to lift at least 200 lbs.
5. Remove the fan sled assembly from the cabinet and
lower onto a flat surface.
6. Remove the bolts holding the fan to the slide-out sled.
7. Remove fan from the slide-out sled.
8. Repeat steps 2-8 for second fan (if equipped).
118