Control Valve Parts Lists - Daikin PreciseLine Series Installation And Maintenance Manual

Table of Contents

Advertisement

Figure 53: ON/OFF Control Valve Wiring
LF24 US
24 VAC Transformer
Line
Volts
On/Off
Figure 54: Modulating Control Valve Wiring
TF24-SR-T US
24 VAC Transformer
Line
Volts
Control Signal (–)
500Ω
VDC/mA (+)
2 to 10VDC (–)
Feedback Signal (+)
2 to 10 VDC / 4 to 20 mA Control

Control Valve Parts Lists

Table 11: ON/OFF Control Valve Part List
Daikin P/N
Valve Type
263940312
2 Way
0.5 FPT
263940304
2 Way
0.5 FPT
263940313
2 Way
0.5 FPT
263940305
2 Way
0.5 FPT
263940314
2 Way
0.75 FPT
263940306
2 Way
0.75 FPT
263940315
2 Way
1.0 FPT
263940307
2 Way
1.0 FPT
263940308
3 Way
0.5 FPT
263940300
3 Way
0.5 FPT
263940309
3 Way
0.5 FPT
263940301
3 Way
0.5 FPT
263940310
3 Way
0.75 FPT
263940302
3 Way
0.75 FPT
263940311
3 Way
1.0 FPT
263940303
3 Way
1.0 FPT
910264701
2-Way
0.5 F-SWT
910282475
2-Way
0.5 F-SWT
910282487
3-Way
0.5 F-SWT
910259925
3-Way
0.5 F-SWT
www.DaikinApplied.com
(Table 11
below)
Blk (1)
Common
Wht (2)
+ Hot
(Table 12 on page
(1)
Common
(2)
+ Hot
(3)
Y Input, 2 to 10V
(5)
U Output
Size
Cv
Control Type
1.9
On/Off
1.9
On/Off
16
On/Off
16
On/Off
24
On/Off
24
On/Off
30
On/Off
30
On/Off
1.9
On/Off
1.9
On/Off
16
On/Off
16
On/Off
24
On/Off
24
On/Off
30
On/Off
30
On/Off
5.9
On/Off
5.9
On/Off
2.7
On/Off
2.7
On/Off
TFRB24
24 VAC Transformer
Line
Volts
On/Off
26)
LRB24-SR
24 VAC Transformer
Line
Volts
Control Signal (–)
500Ω
VDC/mA (+)
2 to 10VDC (–)
Feedback Signal (+)
2 to 10 VDC / 4 to 20 mA Control
Control Voltage
Spring Return
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24V
Yes
24VAC
Yes
24VAC
Yes
24VAC
Yes
24VAC
Yes
25
Blk (1)
Common
Red (2)
+ Hot
Blk (1)
Common
Red (2)
+ Hot
Wht (3)
Y Input, 2 to 10V
Org (5)
U Output
Normal State
Vendor PN (Belimo)
Normally Closed
B211B+TFRB24 DKN
Normally open
B211B+TFRB24 DKN
Normally Closed
B216B+TFRB24 DKN
Normally open
B216B+TFRB24 DKN
Normally Closed
B221B+LF24 DKN
Normally open
B221B+LF24 DKN
Normally Closed
B225+LF24 DKN
Normally open
B225+LF24 DKN
Normally Closed
B311B+TFRB24 DKN
Normally open
B311B+TFRB24 DKN
Normally Closed
B316B+TFRB24 DKN
Normally open
B316B+TFRB24 DKN
Normally Closed
B321B+LF24 DKN
Normally open
B321B+LF24 DKN
Normally Closed
B325+LF24 DKN
Normally open
B325+LF24 DKN
Normally Open
Z2050QS-J+CQKB24-LL DKN
Normally Closed
Z2050QS-J+CQKB24-RR DKN
Normally Open
Z3050QS-H+CQKB24-LL DKN
Normally Closed
Z3050QS-H+CQKB24-RR DKN
IM 1267-7 • PRECISELINE AIR HANDLER