Daikin PreciseLine Series Installation And Maintenance Manual page 33

Table of Contents

Advertisement

Table 19: Vertical Minimum Allowable Air Volume With Electric Heat
kW
006
0.82
300
1
300
1.64
-
2
300
2.45
300
3
300
3.27
-
4
300
4.8
-
4.91
300
6
345
6.54
-
8
-
8.18
-
9.6
-
10
-
12
-
19.2
-
kW
030
6.8
1500
9
1500
11.3
1500
13.5
1500
15
1500
18
1500
21
1500
24
1500
39
2235
NOTE: Limits are based on greater value of either:
1. 250 FPM face velocity across the electric heating coil
2. Entering Air of 70°F and a maximum of 125°F LAT
www.DaikinApplied.com
Unit Size
008
012
Air Volume - CFM
-
-
400
-
400
600
400
600
-
-
-
-
400
600
400
600
400
600
-
-
-
-
400
600
460
600
470
600
550
600
575
600
-
-
-
-
Forward-Curved Fan Units
040
050
Air Volume - CFM
2000
2500
2000
2500
2000
2500
2000
2500
2000
2500
2000
2500
2000
2500
2000
2500
2235
2500
016
020
-
-
-
-
-
-
800
1000
-
-
-
-
800
1000
800
1000
-
-
-
-
-
-
800
1000
800
1000
800
1000
800
1000
800
1000
800
1000
-
1100
Plenum Fan Units
030
040
Air Volume - CFM
1800
2400
1800
2400
1800
2400
1800
2400
1800
2400
1800
2400
1800
2400
1800
2400
1800
2400
33
IM 1267-7 • PRECISELINE AIR HANDLER
Installation
050
3000
3000
3000
3000
3000
3000
3000
3000
3000