Daikin PreciseLine Series Installation And Maintenance Manual page 32

Table of Contents

Advertisement

Table 18: Horizontal Minimum Allowable Air Volume With Electric Heat (unit sizes 030-100)
Forward-Curved Fan Units
kW
030
7.36
1500
9
1500
15
1500
17
-
18
1500
19
-
20
-
21
1500
24
1500
25
-
28.9
-
30
-
32
-
34.4
-
36
-
38
-
39
-
40
-
43.4
-
48
-
50
-
57
-
60
-
63
-
65
-
75
-
95
-
105
-
133
-
NOTE: Limits are based on greater value of either:
1. 250 FPM face velocity across the electric heating coil
2. Entering Air of 70°F and a maximum of 125°F LAT
IM 1267-7 • PRECISELINE AIR HANDLER
040
050
Air Volume - CFM
2000
2500
2000
2500
2000
2500
-
-
2000
2500
-
-
-
-
2000
2500
2000
2500
-
-
-
-
2000
2500
-
-
-
-
2060
2500
-
-
2250
2500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Plenum Fan Units
030
040
050
Air Volume - CFM
1800
2400
3000
1800
2400
3000
1800
2400
3000
-
-
-
1800
2400
3000
-
-
-
-
-
-
1800
2400
3000
1800
2400
3000
-
-
-
-
-
-
-
2400
3000
-
-
-
-
-
-
-
2400
3000
-
-
-
-
2400
3000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
32
Installation
060
080
100
-
-
-
-
-
-
-
-
-
3600
-
-
-
-
-
3600
-
-
3600
-
-
-
-
-
-
-
-
-
4800
-
-
4800
6000
-
4800
6000
3600
-
-
-
-
-
3600
-
-
-
-
-
3600
-
-
-
4800
6000
-
4800
6000
-
4800
-
3600
4800
6000
3600
-
-
3603
4800
6000
-
4800
6000
4290
4800
-
5433
6000
6000
-
6005
-
-
-
7607
www.DaikinApplied.com