Reference Manual
00809-0100-4702, Rev AA
September 2007
Appendix A
SPECIFICATIONS
Functional
Specifications
Physical Specifications
www.rosemount.com
Specifications and
Reference Data
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-1
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-3
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-4
Input
Supports Dry Switch input types. Does not support NAMUR type switches.
Output
Wireless enabled, single or dual switch states or limit or opposing contact
output.
Local Display
The optional five-digit integral LCD Display can display switch status or logic
output. Display updates at transmit rate up to once per minute.
Humidity Limits
0–100% relative humidity
Transmit Rate
User selectable, 15 sec. to 60 min.
Switch Pole Rate
User selectable, 15 sec. to 60 min. same as transmit rate.
Electrical Connections / Battery
•
Replaceable, non-rechargeable, Intrinsically Safe Lithium-Thionyl
Chloride battery pack with PBT enclosure.
•
Eight year battery life at reference conditions.
•
4 Screw Terminals for switch connection.
Field Communicator Connections
Communication Terminals
Clips permanently fixed to terminal block
Materials of Construction
Enclosure
(1) Reference conditions are 70° F (21° C), transmit rate of once per minute, and routing data
for three additional network devices.
Rosemount 702