Reference Manual
00809-0100-4702, Rev AA
September 2007
Figure 2-1. 702 Terminal Block
Figure 2-2. 375 Field
Communicator Connections
The final device network configuration piece is the Update Rate. This by
default is 5 minutes. This may be changed at commissioning, or at any time
via AMS or the 1420 Wireless Gateway's web server. The Update Rate
should be between 15 seconds and 60 minutes. For networks of up to 100
wireless devices, fastest Update Rate is 60 seconds. For networks of 50 or
fewer devices, the fastest Update Rate is 15 seconds
When device configuration is completed, remove the battery and replace the
battery cover. Tighten the cover to the proper tension for safety approvals.
To access the Network Settings using a 375 Field Communicator, enter the
following Fast Key Sequence: 1, 3, 3.
1
2
3
Connect the HART communication leads to the COMM terminals on the
terminal block.
1
2
P/N 00753-9200-0020
3
COMM
4
For HART communication, a 702 DD is required.
Rosemount 702
4
2-3