10.2 Technical Parameter - BT Series

Technical Parameters
Battery Input Data
Battery Type
Nominal Battery Voltage (V)
Battery Voltage Range (V)
Max. Continuous Charging Current
(A)
Max. Continuous Discharging
Current (A)
Max. Charge Power (W)
Max. Discharge Power (W)
AC Output Data (On-grid)
Nominal Apparent Power Output to
Utility Grid (VA)
Max. Apparent Power Output to
Utility Grid (VA)
*1 *6
Nominal Apparent Power from
Utility Grid (VA)
Max. Apparent Power from Utility
Grid (VA)
Nominal Output Voltage (V)
Nominal AC Grid Frequency (Hz)
Max. AC Current Output to Utility
Grid (A)
Max. AC Current From Utility Grid (A)
Nominal Output Current (A)
Power Factor
Max. Total Harmonic Distortion
AC Output Data (Back-up)
Back-up Nominal Apparent Power
(VA)
Max. Output Apparent Power (VA)
Max. Output Current (A)
GW5K-BT
GW6K-BT
Li-Ion
500
180 ~ 600
25
25
5,000
5,000
5,000
5,500
10,000
10,000
400/380,
3L/N/PE
50/60
8.5
15.2
7.2
~1 (Adjustable from 0.8 leading to 0.8 lagging)
<3%
5,000
5,000
(10,000
*2
@60sec)
8.5
73
10 Technical Parameters
GW8K-BT
Li-Ion
Li-Ion
500
500
180 ~ 600
180 ~ 600
25
25
25
25
6,000
8,000
6,000
8,000
6,000
8,000
6,600
8,800
12,000
15,000
12,000
15,000
400/380,
400/380,
3L/N/PE
3L/N/PE
50/60
50/60
10.5
13.5
18.2
22.7
8.7
11.6
<3%
<3%
6,000
8,000
6,000
8,000
(12,000
(15,000
@60sec)
@60sec)
10.5
13.5
GW10K-BT
Li-Ion
500
180 ~ 600
25
25
10,000
10,000
10,000
11,000
15,000
15,000
400/380,
3L/N/PE
50/60
16.5
22.7
14.5
<3%
10,000
10,000
(15,000
@60sec)
16.5