Nameplate - Goodwe ET Series User Manual

Hybrid inverter 5.0-10.0kw ac-coupled inverter 5.0-10.0kw
Hide thumbs Also See for ET Series:
Table of Contents

Advertisement

User Manual V1.1-2022-12-20
Indicator
COM
WiFi
FAULT

3.5.4 Nameplate

The nameplate is for reference only.
Product: Hybrid Inverter
Model
: GW5KN-ET
U
DCma x: 1000Vd.c .
U
MPP : 200...850Vd.c .
PV Input
I
DC,max: 16/16Ad.c.
I
SC PV: 21.2/21.2Ad.c.
U
bat t1 80...600Vd.c.,
Battery
I
batt,max (C/D): 25/25Ad.c.
U
AC,r
3L/N/P E ~ 400/
f
AC, r: 50/60Hz
P
AC, r: 5kW
I
AC,max (to grid): 8.5Aa.c.
S
r (to grid): 5kVA
On-grid
I
AC,max (from grid): 15.2Aa.c.
S
r (from grid): 10kVA
S
max (from grid): 10kVA
U
AC,r 400
/
380V
a.c.
f
AC, r: 50/60Hz
Back-up
I
AC,max: 8.5Aa.c.
S
r:
5kVA
 
S
max: 5kVA
P.F.
T
~1,0.8cap...0.8ind,
Operating: -35~60℃
Non-isolated, IP66, protective Class I, OVC DCII/ACIII
Good We Technologie s Co. , Ltd.
E-mail:service@goodwe.co
m
No.90 Zijin Rd., New District , Suzhou , 21501 1, China
Status
Li-Ion
 
380V
a.c .
ON = Both BMS communication and meter
communication are ok.
BLINK 1 = BMS communication fails; meter
communication is ok.
BLINK 2 = BMS communication is ok; meter
communication fails.
OFF = BMS communicationand meter
communication fail.
ON = WiFi connected / active.
BLINK 1 = WiFi is resetting.
BLINK 2 = WiFi is not connected to the router.
BLINK 4 = WiFi server problem.
OFF = WiFi is not active.
ON = A fault has occurred.
BLINK 1 = Back-up output overload / reduce load.
OFF = No fault.
GW trademark, product type, and product model
Technical parameters
Safety symbols and certification marks
Contact information and serial number
19
03 Product Introduction
Description