9.4 Troubleshooting

Perform troubleshooting according to the following methods. Contact the after-sales service if
these methods do not work.
Collect the information below before contacting the after-sales service, so that the problems can
be solved quickly.
1. Inverter information like serial number, software version, installation date, fault time, fault
frequency, etc.
2. Installation environment, including weather conditions, whether the PV modules are
sheltered or shadowed, etc. It is recommended to provide some photos and videos to assist
in analyzing the problem.
3. Utility grid situation.
No.
Fault
1
Utility Loss
2
Grid Overvoltage
Cause
1. Utility grid power
fails.
2. The AC cable
is disconnected,
or the AC circuit
breaker is off.
The grid voltage
exceeds the
permissible range,
or the duration
of high voltage
exceeds the
requirement of
HVRT.
51
Solutions
1. The alarm is automatically cleared after
the grid power supply is restored.
2. Check whether the AC cable is connected
and the AC circuit breaker is on.
1. If the problem occurs occasionally, the
utility grid may be abnormal temporarily.
The inverter will recover automatically
after detecting that the utility grid is
normal.
2. If the problem occurs frequently, check
whether the grid voltage is within the
permissible range.
• Contact the local power company if the
grid voltage exceeds the permissible
range.
• Modify the overvoltage protection
threshold, HVRT or disable the
overvoltage protection function after
obtaining the consent of the local
power company if the grid frequency is
within the permissible range.
3. Check whether the AC circuit breaker and
the output cables are connected securely
and correctly if the problem persists.