Operation with SIMATIC S5
3.4.2
Jumper Settings on the Actual Value Distributor
1
14
X111
Jumper W1:
CLOSE
OPEN
Jumper W2:
CLOSE
OPEN
Jumper W3:
CLOSE
OPEN
3.4.3
Information about Trouble-Shooting
Please check the following items:
•
Is the address set on the module the same as the one parameterized in FB100?
•
Is the 24V DC power supply for the encoders connected to the actual value distributor
and/or connected directly to the WF 705 module?
•
If no position values are read-out for certain axes or if the values do not change when the
encoder is turned by hand, e.g. 1AAA AAAA or 003A AAA5, check the following:
– whether a read-out has been requested for the axes in question;
– whether the cable break monitor has been triggered;
– whether an encoder has been connected for that axis;
– whether the cable has been connected correctly. If necessary, change the connector.
•
whether jumpers X7 are open except for one module?
•
whether jumpers X8 are open and the encoder cables's screens are generously grounded
(see chapter 4.3)