Description of Device Parameters
Navigation
Description
Reset to factory settings (RES)
Navigation
Description
Note
Device Access Locks.Data Storage Lock
1)
The "Device Access Locks.Data Storage Lock" parameter is an IO-Link standard parameter. The name of the parameter may exist in the configured
language in the IO-Link operating tool used. The display depends on the operating tool in question.
Navigation
Description
Options
40
Parameter → System → Maximum µC-temperature
This parameter is used as the maximum peak indicator and makes it possible to call up ret-
roactively the highest electronics temperature measured.
If the value of the peak indicator is overwritten, the value is automatically set to the tem-
perature currently measured.
Parameter → System → Reset to factory settings (RES)
WARNING
L
Confirming the "Standard Command" with "Reset to factory settings" causes an imme-
diate reset to the factory settings of the order configuration.
If the factory settings have been changed, downstream processes might be affected follow-
ing a reset (the behavior of the switch output or current output might be changed).
Make sure that downstream processes are not started unintentionally.
The reset is not subject to additional locking, such as in the form of device locking. The
reset also depends on the device status.
Any customer-specific configuration carried out at the factory is not affected by a reset
(customer-specific configuration remains).
The following parameters are not reset when a reset is performed:
• Minimum µC-temperature
• Maximum µC-temperature
• Last Diagnostic (LST)
• Operating hours
The last error is not reset in a reset.
1)
Activation/deactivation of DataStorage
Parameter → System → Device Access Locks.Data Storage Lock
The device supports DataStorage. If a device is being replaced, this allows the configuration
of the old device to be written to the new device. If, when a device is being replaced, the
original configuration of the new device is to be retained, the Device Access Locks.Data
Storage Lock parameter can be used to prevent the parameters from being overwritten. If
this parameter is set to "true", the new device does not adopt the data stored in the master' s
DataStorage.
• false
• true
15.4

Observation

The process data are transmitted acyclically.
Liquipoint FTW33