400 Mm Wide Rittal Vx25 And Generic Enclosures - ABB ACS880-304LC Series Hardware Manual

+a019diode supplymodules
Table of Contents

Advertisement

400 mm wide Rittal VX25 and generic enclosures

These figures show 1×D8D and 2×D8D modules in 400 mm wide Rittal VX25 and generic
enclosures. The figures show also pipe routing overviews.
Blue lines
B
Incoming pipes
Red lines
R
Outgoing pipes
Lilac lines
L
Intermediate pipes
Black lines
Electrical connections
In diode supply unit cabinets, flow restrictors are used in both manifolds.
1 supply module: 1×D8D module and the heat exchanger are connected in series in
the cooling circuit. The pipe size is 16/13 mm. See
in 400 mm wide Rittal VX25 enclosure (page
2 supply modules: 2×D8D modules are connected in series, and the heat exchanger is
connected parallel to the modules in the cooling circuit. The pipe size is 16/13 mm
between the modules and the manifolds. The pipe size for parallel connected heat
exchanger is 8/6 mm. See
VX25 enclosure (page
DSU
1xD8D
L
B
R
400
Pipe routing example of 2×D8D unit in 400 mm wide Rittal
42).
Cabinet construction 37
DSU
2xD8D
B
R
L
B
R
400
Pipe routing example of 1×D8D unit
41).
10