128 Technical data
Altitude above sea level
Air temperature
Relative humidity
Contamination
Chemical gases
Solid particles
Vibration
Shock
IEC 60068-2-27:2008,
EN 60068-2-27:2009
Environmental testing -
Part 2-27: Tests - Test Ea
and guidance: Shock
0 ... 2000 m
(0 ... 6561.7 ft) no derat-
ing.
For altitudes over 2000 m
(6561.7 ft), contact ABB.
0 ... +45 °C
(+32 ... +113 °F), no con-
densation allowed. Out-
put derated in the range
+45 ... +55 °C
(+113 ... +131 °F).
Maximum 95%, no con-
densation allowed
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
IEC/EN 60721-3-3:2002:
Classification of environ-
mental conditions - Part
3-3: Classification of
groups of environmental
parameters and their
severities - Stationary
use of weather protected
locations
Class 3C2
Class 3S1
No conductive dust al-
lowed.
IEC 61800-5-1
IEC 60068-2-6:2007,
EN 60068-2-6:2008 Envir-
onmental testing Part 2:
Tests -Test Fc: Vibration
(sinusoidal)
10 ... 57 Hz, max.
0.075 mm amplitude
57 ... 150 Hz 1 g
D8D modules in a
400 mm wide Rittal VX25
enclosure tested in a typ-
ical cabinet assembly,
marine tested according
to:
Max. 1 mm (0.04 in.)
(peak value, 5 ... 13.2 Hz),
max. 0.7 g (13.2 ... 100 Hz)
sinusoidal
Not allowed
-
-40 ... +70 °C
(-40 ... +158 °F)
Maximum 95%, no con-
densation allowed
IEC 60721-3-1:1997
Class 1C2
Class 1S3 (packing must
support this, otherwise
1S2)
IEC/EN 60721-3-1:1997
With packing max.
2
2
100 m/s
(330 ft./s
)
11 ms
-
-40 ... +70 °C
(-40 ... +158 °F)
Maximum 95%, no con-
densation allowed
IEC 60721-3-2:1997
Class 2C2
Class 2S2
IEC/EN 60721-3-1:1997
With packing max.
2
2
100 m/s
(330 ft./s
)
11 ms