Overview Diagram - 2×D8D, 6-Pulse, Internal Charging - ABB ACS880-304LC Series Hardware Manual

+a019diode supplymodules
Table of Contents

Advertisement

Overview diagram – 2×D8D, 6-pulse, internal charging
The diagram shows a supply unit with two D8D modules and internal charging in a
6-pulse connection.
*)
Note:
Each module must have its own input AC cable with the minimum length of 5 meters. Use
symmetrical supply cabling to ensure equal current sharing between parallel diode bridges.
A
External installation (outside supply module cubicle)
B
Supply module cubicle
1
Medium voltage/low voltage switchboard
2
Supply transformer
3
Charging switchgear including disconnecting device
4
Dedicated supply unit switchgear including:
• Disconnecting device
• Breaker/contactor
5
Overcurrent and short-circuit protection of input cabling
6
AC fuses for protecting supply unit against short circuit
7
Internal charging kit
8
Diode supply modules
9
DC link
1)
Available through ABB or third party
2)
Available through ABB
Operation principle and hardware description 21
2)
2)
1)