Close the bleed valve at the cooling unit.
10. Continue to fill in coolant until a base pressure of 100...150 kPa is achieved.
11. Open the bleed valve of the pump to let out any air.
12. Re-check the pressure and add coolant if necessary.
13. Start the coolant pump. Let any air remaining in the system out through the bleed
valve at the cooling unit.
14. After one to two minutes, stop the pump or block the coolant flow with a valve.
15. Re-check the pressure and add coolant if necessary.
16. Repeat steps 13...15 a few times until all air is let out of the cooling circuit. Listen
for a humming sound and/or feel the piping for vibration to find out if there is
still air left in the circuit.
Internal cooling circuit 113