Detailed Parameter Description - WEG MVW3000 Programming Manual

Medium voltage frequency inverter
Hide thumbs Also See for MVW3000:
Table of Contents

Advertisement

4 DETAILED PARAMETER DESCRIPTION

This chapter describes in detail all the parameters of the inverter. In order to simplify the explanation, the parameters
have been grouped by characteristics and functions:
Read-only Parameters
Regulation Parameters
Configuration Parameters
Motor Parameters
Special Function Parameters
Symbols and definitions used in the following text:
(1) Parameter can be changed only with the inverter disabled (motor stopped).
(2) Values may change as a function of the motor parameters.
(3) Values may change as a function of P0412, (Tr Constant).
(4) Values may change as a function of P0296.
(5) Values may change as a function of P0295.
(6) Values may change as a function of P0320.
Torque Current = is the total motor current component responsible for the torque development.
Active current = is the total motor current component proportional to the active electric power consumed by the
motor (in V/F control mode).
P0000 - Parameter access password
Adjustable range:
Description:
It releases access to change the parameter contents.
The access to change the parameter contents is only released when P0000 = current password. The default
password of the inverter is 5; to change teh password, see P0200.
P0001 - Motor speed reference
Description:
It indicates the speed reference value in rpm (factory setting).
Independent from the reference source origin (HMI, serial communication, analog input, among others).
The indication scale can be changed via P0208.
P0002 - Motor Speed
Description:
It indicates the real motor speed value in rpm (with filter with time constant of 0.5 s).
The indication scale can be changed via P0208.
Variables that can be viewed on the graphic HMI, but they cannot be changed by the user
Programmable values used by the inverter functions
They define the inverter characteristics, the functions to be executed, as well as the control board
I/O functions
Used motor data, consisting of information from the motor nameplate
It includes parameters related to special functions
0 to 999
DETAILED PARAMETER DESCRIPTION
Factory setting:
0
4
MVW3000 | 4-1