Please follow the following steps for assembling the AC terminal (M80U
• It is important to choose the proper size for AC cable.
• Strip off all wires for 14 mm.
• The cross-sectional area for each internal cable is 2~2/0 AWG.
Conductor cross-section:
2~2/0 AWG
35 ~ 70mm²
L1
L2
L3
PE
Stripping length:
14 ~16mm
Figure 3-7 : Stripping cables for AC terminal
outer
jacket
23
Installation