Electrical Installation For Ac Wiring - Delta M100A-280 Operation And Installation Manual

Grid-tie transformerless solar inverter
Hide thumbs Also See for M100A-280:
Table of Contents

Advertisement

Installation

3.4 Electrical Installation for AC Wiring

- To avoid shock hazard during cabling, insure any live grid connections are
removed from the inverter.
- Without rain cover, never perform any wiring operations under rainy conditions.
- Code compliance is the installer's responsibility.
- Inverter warranty void if the DC input voltage exceeds 1100 Vdc.
- Installation for AC terminal must meet the local electrical code.
- Failed to follow the instructions may damage AC cable.
- In order not to damage the components in the inverter, ensure the correct
conductor is connected to the appropriate AC terminal on the inverter.
- Please follow the instruction of Section 5.1 to open or close the front door.
- After the wiring operations, please close the door immediately and fully
tighten both toggle latches.
- Please make sure there is no gap between gland and cable.
- Please make sure the gland is tight after setup as shown below.
- Please sealed every entries by duct seal (firemud or
slicon sealant etc.) to avoid water intrution and live
creature entering the inverter.
DANGER : ELECTRICAL HAZARD!!
WARNING !
CAUTION !
ATTENTION
CAUTION !
CAUTION !
28
should not
be loosen!
outer
jacket