57- Exit Device With Inside Keypad, Fire Alarm, Door Status And Remote Horn - Assa Abloy SARGENT Delayed Egress 57-80 Series Installation Instructions Manual

Exit device
Table of Contents

Advertisement

Delayed Egress 57-80 Series
Exit Device
Installation Instructions
9
Sample Wiring Instructions
b

57- Exit Device with inside Keypad, Fire Alarm, Door Status and Remote Horn

A valid code entry at the 4291 (Inside) keypad shunts the 57- exit device and allows egress for a time period
programmable at the keypad. During a fi re alarm condition, the contact opens which de-energizes the external
electromagnet and allows immediate egress. When the rail is armed and the door is forced open, the 3287 door
status switch signals the rail sounding the rail alarm.
Line voltage
fuse (1 AMP)
Voltage adjust for
battery backup
Connector to
power on LED
From transformer
Wiring Notes:
1. Rail, raceway, electric hinge and pigtail 8-pin
connector terminations and wire colors all match.
2. Tape or cap off ends of unused pigtail wires (not
shown) to ensure that they do not short.
3. A fi re alarm tie-in is required on fi re rated openings.
4. The fi re alarm contact (when required) must be
wired to drop 24VDC power to rail. In this case,
terminate fi re alarm contact between the red (+
24VDC) wire and supply + 24VDC output.
ATTENTION:
Electrifi ed Trim applications require a separate raceway and power transfer device. Installation of
conductors or harnesses (by others) through the exit device rail is prohibited as it could lead to
product performance issues up to and including product failure.
1-800-727-5477 • www.sargentlock.com
Copyright © 2005, 2007, 2023, SARGENT Manufacturing Company. All rights reserved. Reproduction in whole or
in part without the express written permission of SARGENT Manufacturing Company is prohibited. Patent pending
and/or patent www.assaabloydss.com/patents.
3520 24VDC 1.0AMP Regulated and Filtered Power Supply
110-120 VAC
NOTE: This drawing shows the
BPS Series. The PM Series
has no line voltage input, fuse
or connector to power on LED
2.5 AMP polyswitch breaker
AC
AC
F
Low voltage AC
Output
Red
Black
Unconnected
terminal for
switch hookup
Plug pigtail harness
connector into
8-pin hinge connector
at frame side
of door
Electric Hinge with
8-pin hinge connector
Raceway harness with
8 & 4-pin connectors.
The 4-pin connectors are not
used here.
(+24),
Red
Normally Closed Fire
Alarm Contact
(If Required)
Battery pack
Green (EG), 4
1584
Electromagnetic
Lock
57- 80 Series Rail
with 8-pin connector
Note: Typical raceway location
is shown. Other locations may
exist depending on door type
2
White (RR), 3
Black (-24), 1
6
4
2
8
7
5
3 1
Pigtail harness
assembly with
8-pin connector
Red (+)
Black (-)
White (C)
3287
Door Status
Switch
4291
Keypad
(Inside)
16
5, Orange (EI)
6, Blue (DS)
-
7, Brown (Mag
)
8, Yellow (Mag +)
-
(
)
C
NO
1 2 3
4 5 6
7 8 9
0 #
(+)
*
A7743F 1/23

Advertisement

Table of Contents
loading

Table of Contents