Trane Tracer VV550 Installation, Operation And Maintenance Manual page 89

Vav controller
Hide thumbs Also See for Tracer VV550:
Table of Contents

Advertisement

Table 60. SCC profile for the Tracer
SCC profile
SCC
Space temperature
Mandatory
Unit status, mode
Mandatory
Unit status, heat
Mandatory
output primary
Unit status, heat
Mandatory
output secondary
Unit status, cool
Mandatory
output
Unit status,
Mandatory
economizer output
Unit status, fan output
Mandatory
Unit status, alarm
Mandatory
present
Effective setpoint
Optional
Effective occupancy
Optional
Heat/cool mode
Optional
Setpoint
Optional
Fan speed
Optional
Discharge air
Optional
temperature
Load, absolute
Optional
Terminal load
Optional
Heat output, primary
Optional
Cool output, primary
Optional
Outdoor air damper
Optional
position
Space relative
Optional
humidity
Outdoor relative
Optional
humidity
Outdoor air
Optional
temperature
Space CO
Optional
2
Effective airflow
Optional
setpoint
Airflow
Optional
Alarm message
Proprietary
Entering water
Proprietary
temperature
Face and bypass
Proprietary
damper position
CNT-SVX17G-EN
Appendix A: Properties, Data Lists Points, and Network Variables
®
VV550/551 controller (continued)
Network variable
nvoSpaceTemp
nvoUnitStatus mode
g
nvoUnitStatus heat
g
output primary
nvoUnitStatus heat
g
output secondary
nvoUnitStatus cool
g
output
nvoUnitStatus econ
g
output
nvoUnitStatus fan output
g
nvoUnitStatus in alarm
g
nvoEffectSetpt
nvoEffectOccup
nvoHeatCool
nvoSetpoint
nvoFanSpeed
nvoDischAirTemp
nvoLoadAbsK
nvoTerminalLoad
nvoHeatPrimary
nvoCoolPrimary
nvoOADamper
nvoSpaceRH
nvoOutdoorRH
nvoOutdoorTemp
nvoSpaceCO
2
nvoEffectFlowSP
nvoAirFlow
nvoAlarmMessage
nvoEnterWaterTmp
nvoFBDamper
Tracer
Standard network
VV550/
variable type (SNVT)
551
SNVT_temp_p
Note
SNVT_hvac_status
Note
Notes 
SNVT_hvac_status
b, h
Notes 
SNVT_hvac_status
b, i
Notes 
SNVT_hvac_status
b, j
SNVT_hvac_status
SNVT_hvac_status
Note
SNVT_hvac_status
Note
SNVT_temp_p
Note
SNVT_occupancy
Note
SNVT_hvac_mode
Note
SNVT_temp_p
Note
SNVT_switch
SNVT_temp_p
Note
SNVT_power_kilo
Present
but
SNVT_lev_percent
always
invalid
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_temp_p
SNVT_ppm
Note
SNVT_flow
Note
SNVT_flow
Note
SNVT_str_asc
Note
SNVT_temp_p
SNVT_lev_percent
®
Tracer Summit
BAS
a
property
b
Space Temperature: Active
b
Mode: Active
Heat Output or Air Valve
Position
Heat Output Secondary
Cool Output or Air Valve
Position
Economizer Damper
Position
Supply Fan Speed or
b
Supply Fan Status
b
Alarm Present
Space Temperature
b
Setpoint: Active
Occupancy: Active 
b
or Mode: Occupancy 
or Occupied Bypass: Active
Mode: Heat/Cool
b
or Heat/Cool Mode: Active
Space Temperature
b
Setpoint: Local
No property
b
Discharge Air Temp
Load: Absolute
Load: Terminal
No property
No property
Outdoor Air Damper
Position
Space Humidity: Input
Outdoor Air Humidity:
Input
Outdoor Air Temperature:
Active
Space CO
Concentration:
2
b
Input
b
Flow Setpoint: Active
b
Airflow: Active
b
Diagnostic Alarm Status
Entering Water
Temperature: Active
Face And Bypass: Active
89

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tracer vv551

Table of Contents