Specifications - Trane Tracer VV550 Installation, Operation And Maintenance Manual

Vav controller
Hide thumbs Also See for Tracer VV550:
Table of Contents

Advertisement

Overview

Specifications

Table 2
controllers.
Table 2. Tracer VV550/VV551 specifications
Specification
Power requirements
Board dimensions
Operating environment
Storage environment
Engineering and agency
requirements
Agency
Agency compliance
Tracer VV551 field mount
controller agency
requirements
8
provides the engineering and agency specifications of the Tracer
Description
Low voltage NEC Class 2, non-safety device
18 to 32 Vac (24 Vac nominal)
Control board, 4 VA
Four outputs, 48 VA maximum
50 or 60 Hz
Note:Trane recommends a separate transformer, fuse, and switch for each controller.
• Height: 5.5 inches (13.97 cm)
• Width: 2 inches (5.08 cm)
• Depth: 4.5 inches (11.43 cm)
0°C to 60°C (32°F to 140°F)
5% to 95% relative humidity noncondensing
–40°C to 85°C (–40°F to 185°F)
5% to 95% relative humidity noncondensing
The following documents specify procedures, ratings, and test levels to demonstrate
compliance to product requirements and C-UL agency requirements.
This controller is a low-voltage class 2, non-safety device.
For factory mounting, the controller is a C-UL unlisted component under UL873.
UL 873/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Tested to IEC standards and Trane engineering standards.
U and C-UL Listing: UL-916-PAZX—energy management
CUL-C22.2—signal devices—Canada
Flammability Rating:Plenum rated per UL 94-5V
FCC:FCC Part 15 Class A emissions compliant
CE:CE-EN61326:1998 Industrial
Certified:
LonMark
®
VV550/VV551
®
CNT-SVX17G-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tracer vv551