Trane Tracer VV550 Installation, Operation And Maintenance Manual page 88

Vav controller
Hide thumbs Also See for Tracer VV550:
Table of Contents

Advertisement

Appendix A: Properties, Data Lists Points, and Network Variables
Table 60
Table 60. SCC profile for the Tracer
SCC profile
SCC
Space temperature
Mandatory
Clear alarms
Mandatory
diagnostics
Setpoint
Optional
Setpoint offset
Optional
Setpoint shift
Optional
Occupancy, schedule
Optional
Occupancy, manual
Optional
command
Occupancy, sensor
Optional
Application mode
Optional
Heat/cool mode
Optional
Fan speed command
Optional
Compressor enable
Optional
Auxiliary heat enable
Optional
Economizer enable
Optional
Valve override
Optional
Flow override
Optional
Emergency override
Optional
Source temperature
Optional
Outdoor air
Optional
temperature
Space relative
Optional
humidity
Space CO
Optional
2
Airflow setpoint
Optional
Binary output request
Proprietary
Outdoor air damper
minimum position
Proprietary
setpoint
Primary secondary
Proprietary
e
Auto commission
Proprietary
command
Discharge air
Proprietary
temperature setpoint
Ventilation ratio limit
Proprietary
Ventilation rate for the
Proprietary
zone
88
describes the SCC profile for the Tracer
®
VV550/551 controller
Network variable
nviSpaceTemp
nviRequest
c
nviSetpoint
nviSetptOffset
nviSetptShift
nviOccSchedule
nviOccManCmd
nviOccSensor
nviApplicMode
nviHeatCool
nviFanSpeedCmd
nviComprEnable
nviAuxHeatEnable
nviEconEnable
nviValveOverride
nviFlowOverride
nviEmergOverride
nviSourceTemp
nviOutdoorTemp
nviSpaceRH
nviSpaceCO
2
nviAirFlowSetpt
Proprietary
Proprietary
Proprietary
Proprietary
nviDischAirStpt
nviVentRatioLim
nviVentSetpt
®
VV550/551 controller.
Tracer
Standard network
VV550/
variable type (SNVT)
551
SNVT_temp_p
Note
SNVT_obj_request
Note
SNVT_temp_p
Note
SNVT_temp_p
SNVT_temp_setpt
SNVT_tod_event
Note
SNVT_occupancy
Note
SNVT_occupancy
Note
SNVT_hvac_mode
Note
SNVT_hvac_mode
Note
SNVT_switch
Note
SNVT_switch
SNVT_switch
Note
SNVT_switch
SNVT_hvac_overid
Note
SNVT_hvac_overid
Note
SNVT_hvac_emerg
Note
SNVT_temp_p
Note
SNVT_temp_p
SNVT_lev_percent
SNVT_ppm
Note
SNVT_flow
Note
Proprietary
Proprietary
Proprietary
Proprietary
Trane
SNVT_temp_p
Note
SNVT_lev_percent
Note
SNVT_flow
Note
®
Tracer Summit
BAS
a
property
b
Space Temperature: Tracer
Node Request or Alarm
b
Reset
b
Space Temperature: Tracer
Setpoint Offset: Tracer
Cooling and Heating
Setpoint Shift: Tracer
d
b
Occupancy: Tracer
b
No property
b
No property
b
Application Mode: Tracer
b
No property
b
No property
Compressor Control:
Tracer
Auxiliary Heat Control:
b
Tracer
Economizer Control: Tracer
Water Valve Override:
b
Tracer
b
Air Flow Override: Tracer
Emergency Override:
b
Tracer
Entering Water
Temperature: Tracer or 
b
Source Temperature:
Tracer
Outdoor air temperature:
Tracer
No property
Space CO
Concentration:
2
b
Tracer
b
Air Flow Stpnt: Tracer
Generic Binary Output:
Tracer
Economizer Min Position:
Tracer
No property
Auto-commissioning Cmd:
f
Tracer
b
No property
Ventilation Ratio Limit:
b
Tracer
Ventilation Setpoint:
b
Tracer
CNT-SVX17G-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tracer vv551

Table of Contents