Table 40.Space temperature controller active minimum airflow setpoint selection (continued)
a
PD
STC mode
Unoccupied
cool
Unoccupied
heat
MWU pre-
cool night
purge
Yes
Occupied
cool
Occupied
heat
CNT-SVX17G-EN
Effective
Control
occupancy
action
b
mode
(PAT)
Unoccupied
Cooling
Heating
Do not care
Cooling
Heating
Occupied
Cooling
Heating
Standby
Cooling
Heating
Local
reheat
Active minimum setpoint (the greatest of the
state
following)
Off
• Zero (air valve closed)
On
• Configured minimum local heating airflow
Off
• Zero (air valve closed)
On
• Configured minimum local heating airflow
Off
• Configured minimum airflow
On
• Configured minimum local heating airflow
• Configured minimum airflow
Off
• Configured minimum heating airflow
On
• Configured minimum local heating airflow
• Configured minimum heating airflow
Off
• Configured minimum airflow
• Ventilation minimum airflow = 0
• Configured minimum position setpoint
On
• Configured minimum local heating airflow
• Configured minimum airflow
• Ventilation minimum airflow = 0
• Configured minimum position setpoint
Off
• Configured minimum heating airflow
• Ventilation minimum airflow = 0
• Configured minimum position setpoint
On
• Configured minimum local heating airflow
• Configured minimum heating airflow
• Ventilation minimum airflow = 0
• Configured minimum position setpoint
Off
• Configured standby minimum airflow
• Ventilation minimum airflow = 0
• Configured minimum position setpoint
On
• Configured minimum local heating airflow
• Configured standby minimum airflow
• Ventilation minimum airflow = 0
• Configured minimum position setpoint
Off
• Configured standby heating minimum airflow
• Ventilation minimum airflow = 0
• Configured minimum position setpoint
On
• Configured minimum local heating airflow
• Configured standby heating minimum airflow
• Ventilation minimum airflow = 0
• Configured minimum position setpoint
Sequence of Operations
61