Sequence of Operations

Heating Operation

Under space temperature control, during the heating mode (communicated heat/cool
mode is heat), the controller attempts to maintain the space temperature at the active
heating setpoint. Based on the controller occupancy mode, the active space heating
setpoint is either the occupied heating setpoint, the occupied standby heating setpoint,
or the unoccupied heat setpoint. Reference
operation during occupied heating and cooling. All ventilation requirements are in force
during occupied heating and cooling.
The outputs are controlled based on the unit configuration and the required heating
capacity. At 0% required heating capacity, the air valve is at its minimum flow setpoint.
As the required heating capacity increases, the air valve opens above its minimum
position. At 100% required heating capacity, the air valve opens to its maximum position.
All units have a modulating air valve. The modulating air valve is used to control how
much air is flowing through the diffusers and into the space. By modulating the volume
of air flowing, the unit heating capacity is modulated.
Units may also have local or remote reheat. This reheat may be hydronic or electric.
Reheat is used to maintain the space temperature at the heating setpoint. For more
information on reheat, refer to
Table 30.Controller operation during occupied heating and cooling
PAT
(a)
Space Temperature
Cold
< Active Heat Stpt
HSP < ZT < HSP + 2
> Active Cool Stpt
Warm
< Active Heat Stpt
< Active Heat Stpt
HSP < ZT < HSP + 2
> Active Cool Stpt
44
"Reheat Control" on page
Primary airflow control active minimum
airflow setpoints
At the highest min position:
• Local heat min airflow
• Min airflow
• Effective ventilation setpoint
At the highest min position:
• Min airflow
• Effective ventilation setpoint
Modulate from cool max to highest min:
• Min airflow
• Effective ventilation setpoint
Modulate from heat max to highest min:
• Local heat min airflow
• Heating min airflow
• Effective ventilation setpoint
Modulate from heat max to highest min:
• Local heat min airflow
• Heating min airflow
• Effective ventilation setpoint
At the highest min position:
• Heating min airflow
• Effective ventilation setpoint
At the highest min position:
• Heating min airflow
• Effective ventilation setpoint
Table 30
for information on controller
45).
Fan control
Series On
Parallel On
Series On
Parallel On
Series On
Parallel Off
Series On
Parallel Off
Series On
Parallel On (w/
reheat)
Series On
Parallel Off
Series On
Parallel Off
Reheat control
Reheat On
Reheat Off
Reheat Off
Reheat Not
Present
Reheat On
Reheat Off
Reheat Off
CNT-SVX17G-EN