Appendix D: Reheat Actuation Schedule Tables
Table 64. Effect of communicated auxiliary heat enable value on heat outputs (continued)
Configuration
Total
number
of heat
Local
Remote
stages
On/Off
On/Off
2
electric
electric
(1 to 2
(1 stage)
stages)
priority
3
On/Off
On/Off
2
hot water
hot water
(1 stage)
(1 stage)
priority
Modulati
ng hot
2
water
On/Off
hot water
(1 stage)
priority
Modulati
On/Off
ng hot
hot water
2
water
(1 stage)
priority
Remote heat priority
2
PWM
On/Off
electric
electric
(1 to 2
(1 stage)
stages
priority
3
100
Commu
nicated
auxiliar
y heat
enable
a
value
Stage 1
Enabled. Limited
by communicated
0.5 to 33
auxiliary heat
enable
0
Disabled
50.5 to
Enabled. On/Off
100
0.5 to 50
Enabled. On/Off
0
Disabled
67.5 to
Enabled. On/Off
100
34 to 67
Enabled. On/Off
0.5 to
Enabled. On/Off
33.5
0
Disabled
50.5 to
Enabled. On/Off
100
0.5 to 50
Enabled. On/Off
0
Disabled
100
Enabled. On/Off
50.5 to
Enabled. On/Off
99.5
0.5 to 50
Enabled. On/Off
0
Disabled
50.5 to
Enabled. No limit
100
50
Enabled. No limit
Enabled. Limited
0.5 to
by communicated
49.5
auxiliary heat
enable
0
Disabled
100
Enabled. On/Off
50.5 to
Enabled. On/Off
99.5
0.5 to 50
Enabled. On/Off
0
Disabled
100
Enabled. On/Off
Stage 2
Stage 3
Disabled
Disabled
Disabled
Disabled
Enabled. On/Off
Not applicable
Disabled
Not applicable
Disabled
Not applicable
Enabled. On/Off
Enabled. On/Off
Enabled. On/Off
Disabled
Disabled
Disabled
Disabled
Disabled
Enabled. On/Off
Not applicable
Disabled
Not applicable
Disabled
Not applicable
Enabled. No limit
Not applicable
Enabled. Limited
by communicated
Not applicable
auxiliary heat
enable
Disabled
Not applicable
Disabled
Not applicable
Enabled. On/Off
Not applicable
Disabled
Not applicable
Disabled
Not applicable
Disabled
Not applicable
Enabled. No limit
Not applicable
Enabled. Limited
by communicated
Not applicable
auxiliary heat
enable
Disabled
Not applicable
Disabled
Not applicable
Enabled. No limit
Enabled. No limit
Unit status,
heat_output_
secondary
0 or
Communicated
auxiliary heat
enable value
0
0, 50, or 100
0 or 50
0
0, 33, 67, or 100
0, 33, or 67
0 or 33
0
0, 50, or 100
0 or 50
0
0 or 50 to 100 (PI
capacity)
0 or 50 to
Communicated
auxiliary heat
enable value (PI
capacity)
0 or 50
0
0 to 50 or 100 (PI
capacity)
0 to 50 (PI
capacity)
0 to
Communicated
auxiliary heat
enable value (PI
capacity)
0
0 to 50 or 100
0, 50 or
Communicated
auxiliary heat
enable value
0 or 50
0
0, 33, 67, or 100
CNT-SVX17G-EN