Appendix C: Mode Control Operation
Table 62. Space temperature control VAV unit operation (continued)
nvi Applic
Mode
nvi Heat Cool
Morning warm-
Don't care
up
Cool
Don't care
Night purge
Don't care
Pre-cool
Don't care
Off
Don't care
Maximum heat
Don't care
Calibrate
Don't care
a.nvoHeatCool/reported unit status mode determined by the controller.
Controller state
Manual output test
Flow override (via nvi or */**) f
Water valve override
Auto-commissioning
Stand-alone air balancing
Calibration
STC: construction
STC: space temperature fails
Emergency override
Unit shutdown
Off
94
a, c
nvoHeatCool
nvoUnitStatus.
nvoEffect
mode
Occup
Unoccupied
Occupied
Morning warm-up
Bypass
Standby
Cool
Unoccupied
Occupied
Bypass
Standby
Unoccupied
Occupied
Night purge
Bypass
Standby
Unoccupied
Occupied
Pre-cool
Bypass
Standby
Unoccupied
Occupied
Off
Bypass
Standby
Unoccupied
Occupied
Maximum heat
Bypass
Standby
Unoccupied
Occupied
Calibrate
Bypass
Standby
Sub state
Step 1
through 8
Output
Operation
b
Air valve
Enabled
Reheat
Enabled
Fan
Enabled
Vent req
Disabled
Air valve
Enabled
Reheat
Enabled
Fan
Enabled
Vent req
Disabled
Air valve
Enabled
Reheat
Enabled
Fan
Enabled
Vent req
Enabled
Air valve
Enabled
Reheat
Disabled
Series fan
Enabled
Parallel fan
Disabled
Vent req
Disabled
Air valve
Enabled
Reheat
Disabled
Series fan
Enabled
Parallel fan
Disabled
Vent req
Disabled
Air valve
Disabled
Reheat
Disabled
Fan
Disabled
Vent req
Disabled
Air valve
Enabled
Reheat
Enabled
Fan
Enabled
Vent req
Disabled
Air valve
Enabled
Reheat
Disabled
Fan
Enabled
Vent req
Disabled
Reported
unit
nvoHeat
status.
Cool
mode
Test
Test
Test
Test
Test
Test
Test
Test
Test
Test
Calibrate
Calibrate
Heat
Heat
Cool
Cool
Don't
Don't care e
care e
Off
Off
Off
Off
Temp control
sequence
STC
Morning warm-up
STC
Unoccupied cooling
STC
Occupied cooling
STC
Pre-cool
STC
Pre-cool
Off
STC
Maximum heat
Calibrate
CNT-SVX17G-EN