Appendix C: Mode Control Operation
Table 62. Space temperature control VAV unit operation (continued)
nvi Applic
Mode
nvi Heat Cool
Morning warm-
Don't care
up
Cool
Don't care
Night purge
Don't care
Pre-cool
Don't care
Off
Don't care
Maximum heat
Don't care
Calibrate
Don't care
a.nvoHeatCool/reported unit status mode determined by the controller.
Controller state
Manual output test
Flow override (via nvi or */**) f
Water valve override
Auto-commissioning
Stand-alone air balancing
Calibration
STC: construction
STC: space temperature fails
Emergency override
Unit shutdown
Off
94
a, c
nvoHeatCool
nvoUnitStatus.
nvoEffect
mode
Occup
Unoccupied
Occupied
Morning warm-up
Bypass
Standby
Cool
Unoccupied
Occupied
Bypass
Standby
Unoccupied
Occupied
Night purge
Bypass
Standby
Unoccupied
Occupied
Pre-cool
Bypass
Standby
Unoccupied
Occupied
Off
Bypass
Standby
Unoccupied
Occupied
Maximum heat
Bypass
Standby
Unoccupied
Occupied
Calibrate
Bypass
Standby
Sub state
Step 1
through 8
Output
Operation
b
Air valve
Enabled
Reheat
Enabled
Fan
Enabled
Vent req
Disabled
Air valve
Enabled
Reheat
Enabled
Fan
Enabled
Vent req
Disabled
Air valve
Enabled
Reheat
Enabled
Fan
Enabled
Vent req
Enabled
Air valve
Enabled
Reheat
Disabled
Series fan
Enabled
Parallel fan
Disabled
Vent req
Disabled
Air valve
Enabled
Reheat
Disabled
Series fan
Enabled
Parallel fan
Disabled
Vent req
Disabled
Air valve
Disabled
Reheat
Disabled
Fan
Disabled
Vent req
Disabled
Air valve
Enabled
Reheat
Enabled
Fan
Enabled
Vent req
Disabled
Air valve
Enabled
Reheat
Disabled
Fan
Enabled
Vent req
Disabled
Reported
unit
nvoHeat
status.
Cool
mode
Test
Test
Test
Test
Test
Test
Test
Test
Test
Test
Calibrate
Calibrate
Heat
Heat
Cool
Cool
Don't
Don't care e
care e
Off
Off
Off
Off
Temp control
sequence
STC 
Morning warm-up
STC 
Unoccupied cooling
STC 
Occupied cooling
STC 
Pre-cool
STC 
Pre-cool
Off
STC 
Maximum heat
Calibrate
CNT-SVX17G-EN