Analog Input Calibration
With the Rover
•
•
•
For each input, the calibration value is added to the measured value to determine the
effective value.
CNT-SVX17G-EN
™
service tool, you can calibrate three controller analog inputs:
Space temperature
Space setpoint
Flow sensor
Space temperature:
±10.0°F at 0.1°F resolution
Space setpoint:
±10.0°F at 0.1°F resolution
Flow:
Calibrated airflow reading = (gain * actual airflow reading) + offset
Gain = configured airflow measurement gain, 0 to 2, at 0.001 resolution
Offset = configured airflow measurement offset, ±50%, at 0.005% resolution
75