Trane Tracer VV550 Installation, Operation And Maintenance Manual page 95

Vav controller
Hide thumbs Also See for Tracer VV550:
Table of Contents

Advertisement

Table 62. Space temperature control VAV unit operation (continued)
nvi Applic
Mode
nvi Heat Cool
Power-up
STC occupied/unoccupied cool
STC occupied/unoccupied heat
VFC (occupied or unoccupied)
Flow tracking
Output
b.
Air valve
Reheat
Fan
Ventilation
Requirements
(Vent req)
c. When communicated application mode is equal to HVAC_TEST, or communicated application mode is equal to HVAC_AUTO
and communicated heat/cool mode is equal to HVAC_TEST, nvoUnitStatus.mode reports HVAC_TEST. The controller
otherwise treats HVAC_TEST the same as HVAC_AUTO for communicated application mode and communicated heat/cool
mode.
d. Zone demand is heat when the space temperature < heat setpoint. Zone demand is cool when the space temperature > cool
setpoint AND space temperature > heat setpoint + 0.5°F.
e. Emergency override leaves nvoHeatCool and nvoUnitStatus.mode as is. Just like Tracer
f. A flow override whether initiated by nviFlowOverride or by star or double star on the zone sensor thumbwheel reports test.
Table 63. Ventilation flow control and flow tracking VAV unit operation
nviApplicMode
nviHeatCool
Auto not valid (any
Auto not valid (any
enumeration not
enumeration not
listed)
listed)
Off
Off
Don't care
a.
Output
Air valve
Reheat
Fan
CNT-SVX17G-EN
a, c
nvoHeatCool
nvoUnitStatus.
nvoEffect
mode
Occup
Zone demand
is cool d
Zone demand
is heat d
Enabled meaning
Control can use air valve
Control can use reheat
Control can run fan
Ventilation requirements are enforced
nvoHeatCool
nvoUnitStatus.mo
de
Cool
Off
Off
Enabled meaning
Control can use air valve
Control can use reheat
Control can run fan
Appendix C: Mode Control Operation
Output
Operation
b
Cool
Cool
Heat
Heat
Cool
Cool
Cool
Cool
Disabled meaning
Air valve is closed
Reheat is Off
Fan is Off
Ventilation requirements are
waived (air valve may close)
®
ZN510/520.
nvoEffectOccup
Outputs
Unoccupied
Air valve
Occupied
Reheat
Bypass
Fan
Standby
Unoccupied
Air valve
Occupied
Reheat
Bypass
Fan
Standby
Unoccupied
Air valve
Occupied
Reheat
Bypass
Fan
Standby
Disabled
meaning
Air valve is closed
Reheat is Off
Fan is Off
Temp control
sequence
a
Operation
Enabled
Enabled
b
Not present
Disabled
Disabled
b
Not present
Disabled
Disabled
b
Not present
95

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tracer vv551