Table 64. Effect of communicated auxiliary heat enable value on heat outputs (continued)
Configuration
Total
number
of heat
Local
Remote
stages
On/Off
2
On/Off
electric
electric
(1 to 2
(1 stage)
stages)
priority
3
2
On/Off
On/Off
hot water
hot water
(1 stage)
(1 stage)
priority
Modulati
2
On/Off
ng hot
hot water
water
(1 stage)
priority
Modulati
ng hot
2
water
On/Off
hot water
(1 stage)
priority
a. The value of the PI capacity loop (total unit capacity) is limited by communicated auxiliary heat enable.
CNT-SVX17G-EN
Commu
nicated
auxiliar
y heat
enable
a
value
Stage 1
67.5 to
Enabled. On/Off
99.5
67
Enabled. On/Off
34 to
Enabled. On/Off
66.5
0.5 to
Enabled. On/Off
33.5
0
Disabled
50.5 to
Enabled. On/Off
100
0.5 to 50
Enabled. On/Off
0
Disabled
67.5 to
Enabled. On/Off
100
34 to 67
Enabled. On/Off
0.5 to
Enabled. On/Off
33.5
0
Disabled
50.5 to
Enabled. On/Off
100
0.5 to 50
Enabled. On/Off
0
Disabled
50.5 to
Enabled. No limit
100
50
Enabled. No limit
Enabled. Limited
0.5 to
by communicated
49.5
auxiliary heat
enable
0
Disabled
100
Enabled. On/Off
50.5 to
Enabled. On/Off
99.5
0.5 to 50
Enabled. On/Off
0
Disabled
Appendix D: Reheat Actuation Schedule Tables
Stage 2
Stage 3
Enabled. Limited
by communicated
Enabled. No limit
auxiliary heat
enable
Enabled. No limit
Disabled
Enabled. Limited
by communicated
Disabled
auxiliary heat
enable
Disabled
Disabled
Disabled
Disabled
Enabled. On/Off
Not applicable
Disabled
Not applicable
Disabled
Not applicable
Enabled. On/Off
Enabled. On/Off
Enabled. On/Off
Disabled
Disabled
Disabled
Disabled
Disabled
Enabled. On/Off
Not applicable
Disabled
Not applicable
Disabled
Not applicable
Enabled. On/Off
Not applicable
Disabled
Not applicable
Disabled
Not applicable
Disabled
Not applicable
Enabled. No limit
Not applicable
Enabled. Limited
by communicated
Not applicable
auxiliary heat
enable
Disabled
Not applicable
Disabled
Not applicable
Unit status,
heat_output_
secondary
0, 33, 67, or
Communicated
auxiliary heat
enable value
0, 33, or 67
0, 33, or
Communicated
auxiliary heat
enable value
0 or 33
0
0, 50, or 100
0 or 50
0
0, 33, 67, or 100
0, 33, or 67
0 or 33
0
0, 50, or 100
0 or 50
0
0 to 50 or 100 (PI
capacity)
0 to 50 (PI
capacity)
0 to
Communicated
auxiliary heat
enable value (PI
capacity)
0
0 or 50 to 100 (PI
capacity)
0 or 50 to
Communicated
auxiliary heat
enable value (PI
capacity)
0 or 50
0
101