Specifications and Dimensions

Table 1. UC400/UC400–B Specifications
Storage
Temperature:
Relative Humidity:
Operating
Temperature:
Humidity:
Input Power:
Mounting Weight of
Controller:
Environmental Rating
(Enclosure):
Altitude:
Installation:
Pollution:
Housing Material:
(a)
Mounting:
Agency Listing
UL916 PAZX, Open Energy Management Equipment
UL94-5V, Flammability
CE Marked
FCC Part 15, Subpart B, Class B Limit
AS/NZS CISPR 22:2006
VCCI V-3/2008.04
ICES-003, Issue 4:2004
®
Communications BACnet
MS/TP, supports BACnet Protocol ASHRAE 135-2004 and Meets BACnet Testing Laboratory (BTL) as an Application
Specific Controller (ASC) Profile Device
(a)
Not applicable for the UC400-B model.
BAS-SVX48H-EN
–48°F to 203°F (–44°C to 95°C)
Between 5% and 95% (non-condensing)
–40°F to 158°F (–40°C to 70°C)
Between 5% and 95% (non-condensing)
20.4–27.6 Vac (24, ±15% nominal), 50Hz to 60Hz, 24 VA
(24 VA plus binary output loads for a maximum of 12 VA for each binary output)
Supporting mounting surface: must be 0.80 lb. (.364 kg)
NEMA 1
6,500 ft. maximum (1,981 m)
U.L. 840: Category 3
U.L. 840: Degree 2
Polycarbonate/ABS Blend
UV protected
U.L. 94-5VA flammability rating
UC400: Mounts on EN 50 022 - 35 X 15 DIN rail.
UC400–B: Pre-mounted.