Chapter 3
Module Tag Definitions
Access the Tags
Configuration Assembly
24
You view tags from the Configuration Tags.
1. Open your Studio 5000 Logix Designer application project.
2. Right-click Controller Tags and choose Monitor Tags.
3. Open the tags as necessary to view specific tags.
The ASCII modules support a configuration assembly that is accessed through
the Assembly Object (Class 4), Instance 103. The configuration assembly is
18 bytes.
Table 7 - Configuration Assembly
Byte
Parameter
0
ASCII Serial Character Format
1
ASCII Serial Comm Speed
2
ASCII Max Number of Receive Characters
3
ASCII Receive Record Start Mode
4
ASCII Receive Start Delimiter
5
ASCII Receive Record End Mode
6
ASCII Receive End Delimiter
7
ASCII Receive String Data Type
8
ASCII Pad Mode
9
ASCII Pad Character
10
ASCII Receive Swap Mode
11
Ethernet Handshake Mode
12
ASCII Max Number of Transmit Characters
Rockwell Automation Publication 1734-UM009C-EN-P - August 2022
(1)
Parameter Instance
1
2
3
4
5
6
7
8
9
10
11
12
17