  • Page 1 User Manual ControlLogix Time Syncronization Module - Series B Catalog Number 1756HP-TIME Allen-Bradley Motors...
  • Page 2 Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE). Allen-Bradley, ControlFLASH, ControlLogix, Logix5000, RSLogix, Studio 5000 Automation Engineering & Design Environment, Studio 5000, Studio 5000 Logix Designer, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
  • Page 3: Table Of Contents

    Dimensions............33 Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 4 ..............49 Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 5: Studio 5000 Environment

    Global Positioning System (GPS) technology. The 1756HP-TIME module can obtain time from various sources, and provide time synchronization on other devices by acting as a gateway between different time synchronization methods and standards. Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 6: Additional Resources

    Provides declarations of conformity, certificates, and other certification details. You can view or download publications at http:/www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 7: Hardware

    GPS Antenna on page IRIG-B coaxial connector Connect the IRIG-B network cable to this connector. The 1756HP-TIME module Allen-Bradley Motors can be configured as a master clock or a slave clock on the IRIG-B network. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 8: Gps Antenna

    Use this software to configure and operate the 1756HP-TIME module: • The Studio 5000 Logix Designer application • The Add-on Profile (AOP) for the 1756HP-TIME module, available for download at this link: http://www.hiprom.com/Pages/Products/1756_CLX/1756HP-TIME/ web/1756HP-TIME.htm Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 9: Bootp

    The display informs you of the error and suggests a method to fix the error. If there is a firmware error, use the ControlFLASH software to restore the module to a working condition. Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 10: Controlflash Software

    Follow these steps to configure the 1756HP-TIME module in the Logix Designer application. 1. Double-click the 1756HP-TIME module in the I/O tree in the Logix Designer application. The New Module dialog box appears. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 11 7. Select the Time Output format. 8. Enter the Advanced CIP Sync Settings. 9. Enter the Description Settings. 10. Click OK. The time properties of the 1756HP-TIME module are now configured. Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 12: View The Satellite Status In The Logix Designer Application

    Figure 4 - 1756HP-TIME Module Properties Dialogue Box, Advanced Tab Satellite Signal Click Sat. Signal to view the signal strength of the satellites. Figure 5 - 1756HP-TIME Module Properties Dialogue Box, Sat. Signal Node Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 13: Satellite Position

    1756HP-TIME Module AOP This section describes the AOP configuration parameters for the 1756HP-TIME module. This section is for information purposes. The AOP is used to configure Configuration Parameters all the relevant module parameters. Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 14 Allowed values: 1/2 = 500 ms 1 = 1 second 2 = 2 seconds AdvancedConfig These are various bits used to set certain options in the module. Bit: 0 =Simulation Mode 1…31 = Reserved Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 15 Use this parameter to identify the time module, visible in CIP sync synchronization. Example: 1756HP-TIME UserLocation Use this parameter to provide extra information to identify the location of the module. Example: Basement Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 16 Chapter 2 Setup Notes: Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 17: Logix5000 Controller Input Image

    Logix5000 Controller Output Image Web Interface Logix5000 Controller Input Each 1756HP-TIME module consumes one connection from the Logix5000 controller. This section provides descriptions for the Logix5000 controller input Image image parameters. Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 18 Displays the current hour received from the time source. Example: 27/04/2010 13:45:22 - 234567 μs Hour = 13 Time.Minute Displays the current minute received from the time source. Example: 27/04/2010 13:45:22 - 234567 μs Minute = 45 Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 19 Displays the current position longitude in degrees. Example: S26°05'17.0" E28°00'21.3" Elev: 1577m Longitude = 28.00586 GPS.Altitude Displays the current position altitude in meters. Example: S26°05'17.0" E28°00'21.3" Elev: 1577m Elevation = 1577 Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 20: Logix5000 Controller Output Image

    Atomic Time (TAI). The difference between the two is the UTC offset. Be sure to verify the current UTC offset. The UTC offset changes approximately every 18 months. ReferencePositionX Reserved. – ReferencePositionY Reserved. – ReferencePositionZ Reserved. – Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 21: Web Interface

    Enter http:// and the IP address of the 1756HP-TIME module into the address bar of your web browser. For example, enter the IP address as shown here. The web interface provides diagnostics and statistics for the 1756HP-TIME module. Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 22 Chapter 3 Operation Notes: Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 23: 1588 Precision Time Protocol (Cip Sync)

    Therefore, the more switches and interfaces between the 1756HP-TIME module and the devices being synchronized, the bigger the spread of random time delays Allen-Bradley Motors that can result in lower time sync accuracy. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 24: Configure The Ethernet Module/Controller Ptp/Cip

    Follow these steps to configure the PTP/CIP Sync settings of the 1756-EN2T/ 1756-EN2TR module and controller. 1. Open the AOP for the Ethernet module. 2. From the General tab, under Module Definition, click Change. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 25 The Logix5000 controller looks for the highest-quality clock on the backplane. 7. Click OK. The settings of the Ethernet module and controller module are now configured for time sync and motion. Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 26: Ptp As A Time Source

    The 1756HP-TIME module supports NTP version 3, RFC1305. When a computer is on a domain, it tries to synchronize to the domain IMPORTANT controller. Therefore, you can set up the domain controller to synchronize to the 1756HP-TIME module. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 27 8. Click NTP Source Sync to synchronize the time with the NTP server. The Windows time service is now configured to synchronize to the 1756HP-TIME module. To reset the defaults, click Set next to ‘Resort to defaults’ . Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 28: 1756Hp-Time Module As An Ntp Client

    1756HP-TIME module. If the time is not adjusted by the NTP source, the time can drift by up to 10 μs/s depending on external factors, such as temperature and humidity. 6. Click OK. The 1756HP-TIME module is now configured to an NTP source. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 29: Irig-B

    The accuracy of the NTP time depends on the quality and reliability of the IMPORTANT Ethernet network. If the update time is set too high, the clock can drift and jump. Rockwell Automation recommends a value of 30 seconds or less for optimal accuracy. Loss of Communication...
  • Page 30: 1756Hp-Time Module As An Irig-B Slave

    Conversion Message Blocks on page 37 for these message formats. The CST offset can also be used to adjust the wallclock by using a set system values (SSV) instruction to pass the CST offset. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 31: Technical Specifications

    Type RG58 or equivalent Impedance 50 Ω Shield Foil or copper braid (100% coverage) Connectors SMA male to TNC male Signal attenuation At 1.5 GHz < 10 dB (less than 6 dB recommended) Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 32: Gps Antenna Specifications

    For more information about the Trimble Bullet III 3.3V GPS antenna, part number 57861-20, visit the Trimble website at http://www.trimble.com/. Contact a Trimble sales representative to purchase the Trimble Bullet III 3.3V IMPORTANT GPS antenna. Rockwell Automation does not provide GPS antennas. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 33: Dimensions

    Specifications Appendix A Dimensions This drawing shows the dimensions of the 1756HP-TIME module. Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 34 Appendix A Specifications Notes: Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 35: Status Indicators

    Green = the module is locked on the time source. SYNC Red = the module is not locked on the time source. Green = the module has started successfully. Red = the module has a hardware fault. Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 36: Status Messages

    BL. Err X - Y code, and Y is the description of the error. An error has occurred during operation. X is the error code, and Y Err X - Y is the description of the error. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 37: Cst To Utc And Gregorian Time Conversion

    Value Message type CIP generic Service type Custom Service code Message settings Class Instance Attribute Source element Event_UTC[0] Date elements Source length Destination Event.Year Allen-Bradley Motors (1) See the example code at http://www.hiprom.com/. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 38: Satellite Information

    Settings and Elements Attribute Value Message type CIP generic Service type Custom Service code Message settings Class Instance Attribute Source element Date elements Source length Destination SatInformation[0].PRN (1) See the example code at http://www.hiprom.com/. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 39: Gps Source

    NTP Source GPS Source The GPS source mode can have the following configurations: • Source: GPS • Outputs: IRIG-B, 1588 PTP/CIP Sync, NTP, and input/output assemblies. 1588 PTP GPS Antenna IRIG-B Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 40: Irig-B Source

    IRIG-B PTP Source The PTP source mode can have the following configurations: • Source: 1588 PTP/CIP Sync, either over Ethernet or the backplane • Outputs: IRIG-B, NTP, and input/output assemblies 1588 PTP IRIG-B Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 41: Ntp Source

    Operating Modes Appendix D NTP Source The NTP source mode can have the following configurations: • Source: NTP, over Ethernet • Outputs: IRIG-B, 1588 PTP/CIP Sync, and input/output assemblies 1588 PTP IRIG-B Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 42 Appendix D Operating Modes Notes: Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 43: Cable Extensions

    Cable Extensions The 1756HP-TIME module ships with a 5 m (16 ft) RG58 coaxial cable. Rockwell Automation does not supply longer cables. If you need a longer cable for your installation, follow the guidelines in this appendix to specify and purchase extensions from a cable supplier.
  • Page 44: Example - Determining Cable Requirements

    If the attenuation from a lower loss cable (such as LMR 600) is greater than 10 dB, you need to use an amplifier. Rockwell Automation does not supply amplifiers. If you need an amplifier for your installation, follow the guidelines in this appendix to specify and purchase an amplifier from a cable supplier.
  • Page 45: Lightning Protection Devices

    RG58-TT-6 15 dB Lightning Protection Devices Rockwell Automation recommends lightning protection devices that are capable of receiving multiple strikes, with a clamping voltage above the 3.3V DC that is required by the antenna (such as a Polyphaser DGXZ+06NFNF device). Mount the lightning protection device outside, with an earth ground.
  • Page 46: Rockwell Automation Publication 1756-Um542A-En-P - September

    Appendix E GPS Antenna Cable Extensions Notes: Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 47 (as well as positioning and navigation) on a continuous basis in all weather, day and night, anywhere on or near the Earth that has an unobstructed Allen-Bradley Motors view of four or more GPS satellites. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 48 The time does not include time zone or Daylight Saving Time offsets. System time is the same as UTC. WallClockTime (WCT) WallClockTime is the time of the controller based on UTC system time. Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 49 7 multicast address 24 diagnostics 21 dimensions NTP 6 1756HP-TIME module 33 client 26 GPS antenna 32 output 18 domain controller 26 server 14 source 28 version 3, RFC1305 26 Allen-Bradley Motors Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 50 12 output 12 source 12 sync accuracy 23 synchronization methods, standards, and protocols 6 time format conversion CST to Gregorian 30 CST to UTC 37 UTC to Gregorian 30 transparent gateway 24 Rockwell Automation Publication 1756-UM542A-EN-P - September 2014...
  • Page 51 Allen-Bradley Motors...
  • Page 52 New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

This manual is also suitable for:

1756hp-time

Table of Contents