Troubleshoot the Module

Chapter Summary

Publication 1734-UM004F-EN-E - December 2012
Indicator Sta
tus for Module
s
Status
Network status Off
Flashing green
Green
Flashing red
Red
Flashing
red/green
Channel status Off
Solid green
Flashing green
Solid ged
Flashing ged
This module is not field repairable. Any attempt to open this
IMPORTANT
module will void the warranty. If repair is necessary, return this
module to the factory.
This chapter helped you to interpret the status indicators on the modules.
Refer to the Appendix to learn how to configure the POINT I/O
Thermocouple and RTD Modules using the RSLogix 5000 software.
Description
Device is not online.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status
indicator.
Device is online but has no connections in the
established state.
Device online and has connections in the
established state.
One or more I/O connections are in timed-out
state.
Critical link failure is present with failed
communication device. Device detected error that
prevents it from communicating on the network.
Communication faulted device - the device
detected a network access error and is in
communication faulted state. Device received and
accepted an Identify Communication Faulted
Request - long protocol message.
Module is in CAL mode.
Normal state is present with channel scanning
inputs.
Channel being calibrated.
Major channel fault is present.
Channel is at end of range (over or under).