Rockwell Automation Allen-Bradley 1734-IR2 User Manual page 74

Point i/o thermocouple and rtd modules
Table of Contents

Advertisement

64
Configure Modules in RSLogix 5000 Software
Publication 1734-UM004F-EN-E - December 2012
For This Value
Select
Low Engineering
-32,768...32,767.
Digital Filter (ms)
0...10000.
Notch Filter
50 Hz
60 Hz
100 Hz
120 Hz
200 Hz
240 Hz
300 Hz
400 Hz
480 Hz
Cold Junction Enable
Click to check the
checkbox
Cold Junction Offset
0.00...70.00
(°C)
Cold Junction Notch
50 Hz
Filter
60 Hz
Cold Junction Mode
None
Channel 0
Channel 1
Average Both
Alarm Configuration Dialog
This dialog does not appear for Listen-Only options. The dialog displays alarm
configuration parameters for each channel in individual rows on the grid. To
complete entries on this dialog, proceed as follows.
1. Click Alarm Configuration to display the dialog.
Comments
Default is 1000.
This is enabled when you select Custom
Scale for Temperature Units.
Default is 0.
Default is 60 Hz.
If checked the Cold Junction feature is
enabled.
Select a value to configure the value for
cold junction offset.
You enable this feature when you check
Cold Junction Enable.
This feature is disabled in Hard Run mode.
Default is 0.
Select the value for Cold Junction Notch
Filter.
Default is 60 Hz.
Select a value for Cold Junction Mode.
Default is channel 0.