Calibrate Your Module

Input (mV) Calibration

Publication 1734-UM004F-EN-E - December 2012
4. From the Device Parameters dialog, select Calibration at the Groups
pull-down.
Before calibrating the module you need to select the sensor type and download
it to the module.
Perform the following procedure from the Device Parameters dialog.
Apply power to the power supply and module for at least 10
IMPORTANT
minutes before calibrating the module.
Delete all I/O connections by removing the module from its
master's scan list and inhibiting the module in RSLogix. When
there is no connection present the Network Status Indicator
should flash green.
This is the Groups pull-down.