The 1734-IT2I module consists of two isolated millivolt inputs (+70 mV).
Configure the module to do the linearization necessary for thermocouple
inputs. See the table for a list of supported thermocouple input types.
Supported Sensor Types – Thermocouple
mV (default) -70...+70 mV
B
572...3272 °F
C
32...4199 °F
E
-418...+1832 °F
J
-346...+2192 °F
K
-418...+2502 °F
N
-418...+2372 °F
R
32...3214 °F
S
32...3214 °F
T
-418...+752 °F
The 1734-IR2 consists of two RTD inputs (0...600 W). Configure the module
to do the linearization necessary for RTD inputs. See the table for a list of
supported input types.
Supportted Sensor Types – RTD
α = 0.00385 Euro
100 Pt
α = 0.00385 Euro
200 Pt
α = 0.003916 U.S.
100 Pt
α = 0.003916 U.S.
200 Pt
α = 0.00427
10 Cu
α = 0.00618
100 Ni
α = 0.00618
120 Ni
α = 0.00672
120 Ni
The 1734-IR2E consists of two RTD inputs (0...200 W). Configure the module
to do the linearization necessary for RTD inputs. See the table for a list of
supported input types.
I/O messages are sent to (consumed) and received from (produced) the
POINT I/O modules. These messages are mapped into the processor's
memory. The Thermocouple input module produces 8 bytes of input data
(scanner Rx) and fault status data. It does not consume I/O data (scanner Tx).
The RTD input module produces 6 bytes of input data (scanner Rx) and fault
status data. It does not consume I/O data (scanner Tx).
(300...1800 °C)
(0...2315 °C)
(-250...+1000 °C)
(-210...+1200 °C)
(-250...+1372 °C)
(-250...+1300 °C)
(0...1768 °C)
(0...1768 °C)
(-250...+400 °C)
-328...1598 °F
-328...1166 °F
-328...1166 °F
-328...1166 °F
-328...500 °F
-76...+482 °F
-76...+482 °F
-76...+482 °F
(-200...+870 °C)
(-200...+630 °C)
(-200...+630 °C)
(-200...+630 °C)
(-200...+260 °C)
(-60...+250 °C)
(-60...+250 °C)
(-60...+250 °C)

Advertisement